Manufacturers

Kyoritsu 5410 RCD Tester

  • Model: KE 5410
  • Shipping Weight: 0.965kg
  • Manufactured by: KYORITSU

RM3,900.00

Add to Cart:

Measurement of RCD trip time
Conducting testing of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges.

Measurement of trip out current
Measuring trip out current by varying current automatically.

Remote Test
Enabling a user to hold the Test Leads with his both hands by locking the Test Button. Measurement will automatically start when the main voltage is detected.

Voltage Measurement
Carrying out a constant measurement of voltage in the stand-by mode at each Range.

 


 

 

Auto-detection of Contact voltage
Detecting the voltage to earth of Earth electrodes or Protective conductors during RCD test - when applying test currents - at measurement using EARTH in order to prevent electrical shocks caused by the damaged earth. Measurement will be ceased at AC50V or more.

Dust- and Water-proof
Dust- and Water-proof construction (designed to IEC 60529 IP54).

Backlight
Facilitating working at dimly illuminated locations.

 

 

Measurement of RCD trip time - Measurement of trip out current

Range

×5

×1

×1/2

AUTO RAMP (mA)

Rated Voltage

100V±10%
200V+32%/-10%
400V±10%
(50/60Hz)

Test current

15/30/50/100mA

15/30/50/100/200/500mA

15/30/50/100/200/500mA

Measuring range

Testing time
200ms

Testing time
2000ms

Testing time
2000ms

40%~110% of lΔn
(goes up by 5%)
Testing time
300ms × 15steps

Accuracy
(Trip Time)

|±1%rdg±3dgt

|±1%rdg±3dgt

|±1%rdg±3dgt

Test Current
at each step
-4%~+4%

Accuracy
(Test Current)

|+2%~+8%dgt

|+2%~+8%dgt

|-8%~-2%dgt

Voltage Measurement

Measuring range

80V~450V (50/60Hz)

Accuracy

|±2%rdg±4dgt

 

Applicable Standard

IEC 61010-1 Pollution degree2 CAT.III 300V / CAT.II 400V
IEC 61010-031
IEC 61557-1, 6
IEC 60529 (IP54)

Display

1999 counts (3 1/2digits), Large LCD

Operating temperature & humidity

0ºC~40ºC, relative humidity 85% (no condensation)

Storage temperature & humidity

-20ºC~60ºC, relative humidity 85% (no condensation)

Withstand Voltage

AC3700V / 1 min. (between electrical circuit and enclosure)

Insulation resistance

50MΩ or more / 1000V (between electrical circuit and enclosure)

Sleep Function

(1)

Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn't work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted.

(2)

Backlight turns off in 1 minute after it lights up.

 

Power Source

DC 12V / Size AA battery R6P (SUM-3) × 8 pcs.

Dimension

186(L)×167(W)×89(D)mm

Weight

Approx. 965g (including batteries)

Possible number of Measurements

1200 times or more
(measure every 30 seconds at ×1/2 Range, lΔn=100mA)

Accessories

7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Long pin) × 2
Cord case, Strap belt, Instruction manual,
Size AA battery R6P(SUM-3)×8pcs.

(*)

Only the RCD type G (without trip out time-delay) can be tested at Auto Ramp Test,type S (time-delay) cannot be tested.

This product was added to our catalog on Thursday 01 January, 1970.

Who's Online

There currently are 296 guests online.
Your IP Address is: 18.189.14.219
Copyright © 2024 Techno Tools*** About Us***mobile link***Desktop link