Fluke 1503 Insulation Tester

RM2,652.00  RM2,449.00
Save: 8% off

The Fluke 1507 and 1503 Insulation Testers are compact, rugged, reliable, and easy to use. With their multiple test voltages, they are ideal for many troubleshooting, commissioning, and preventative maintenance applications.

 

Additional features, like the remote probe on these tools save both time and money when performing tests.

 

Features and benefits of the Fluke 1503

  • Insulation test range:
    • 1507: 0.01 MΩ to 10 GΩ
    • 1503: 0.1 MΩ to 2000 MΩ
  • Insulation test voltages:
    • 1507: 50 V, 100 V, 250 V, 500 V, 1000 V
    • 1503: 500 V, 1000 V
  • Save both time and money with Automatic calculation of Polarization Index and Dielectric Absorption Ratio (only available on the1507)
  • Make repetitive tests simple and easy with the 1507’s Compare (Pass/Fail) function (only available on the 1507)
  • Repetitive or hard-to-reach testing is easy with the remote test probe
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • Auto-discharge of capacitive voltage for added user protection
  • AC/DC voltage: 0.1 V to 600 V
  • 200 mA Continuity
  • Resistance: 0.01 Ω to 20.00 kΩ
  • Save battery power with auto power off
  • Read measurements easily with large, backlit display
  • CAT IV 600 V overvoltage category rating for added user protection
  • Remote probe, test leads, probes and alligator clips included with each tester
  • Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
  • Four AA alkaline batteries (NEDA 15 A or IEC LR6) for at least 1000 insulation tests
  • One year warranty

 

 

 

 

 

AC/DC Voltage Measurement

Accuracy

Range

 600.0 V

Resolution

 0.1 V

50 Hz to 400 Hz ± (% of Rdg + Digits)

 ± (2 % + 3)

Input impedance

 

 3 MΩ (nominal), < 100 pF

Common mode rejection ratio (1 kΩ unbalanced):

 

 > 60 dB at dc, 50 or 60 Hz

Overload Protection

 

 600 V rms or dc

Earth bond resistance measurement

Range/Resolution

20.00 Ω

 0.01 Ω

200.0 Ω

 0.1 Ω

2000 Ω

 1.0 Ω

20.00 kΩ

 0.01 kΩ

Accuracy

 

 ± (1.5 % + 3)

Overload Protection

 

 2 V rms or dc

Open Circuit Test Voltage

 

 > 4.0 V, < 8 V

Short circuit current

 

 > 200.0 mA

Insulation specifications

Measurement Range

1507:

 0.01 MΩ to 10 GΩ

1503:

 0.01 MΩ to 2000 MΩ

Test voltage

1507:

 50 V, 100 V, 250 V, 500 V, 1000 V

1503:

 500 V, 1000V

Test Voltage Accuracy

 

 + 20 %, - 0 %

Short circuit current

 

 1 mA nominal

Auto Discharge

 

 Discharge time < 0.5 second for C = 1 µF or less

Live circuit indicator

 

 Inhibit test if terminal voltage > 30 V prior to initialization of test

Maximum Capacitive Load

 

 Operable with up to 1 µF load

Measure Accuracy:

50 V:

 ±(3 % + 5)

100 V:

 ±(3 % + 5)

250 V:

 ±(1.5 % + 5)

500 V:

 ±(1.5 % + 5)

1000 V:

 ±(1.5 % + 5) to 2000 MΩ, ±(10 % + 3) above 2000 MΩ

 

General Specifications

Maximum voltage applied to any terminal:

 

 600 V ac rms or dc

Storage Temperature

 

 -40 °C to 60 °C (-40 °F to 140 °F)

Operating Temperature

 

 -20 °C to 55 °C (-4 °F to 131 °F)

Temperature Coefficient

 

 0.05 x (specified accuracy) per °C for temperatures < 18 °C or > 28 °C (< 64 °F or > 82 °F)

Relative Humidity

 

 0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F)

 

 0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F)

 

 0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F)

Vibration

 

 Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument

Shock

 

 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor)

Electromagnetic compatibility:

 

 In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997)

Safety

 

 Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV)

Certifications:

 

 CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition

Batteries

 

 Four AA batteries (NEDA 15A or IEC LR6)

Battery Life

Insulation test use:

 Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off.

Resistance measurements:

 Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off.

Size

 

 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L)

Weight

 

 550 g (1.2 lb)

IP Rating

 

 IP40

Altitude

Operating:

 2000 m CAT IV 600 V, 3000 m CAT III 600 V

Non-operating (storage):

 12,000 m

Over-range capability:

 

 110 % of range


Add to Cart:

  • Model: FLUKE-1503
  • Shipping Weight: 1.35kg
  • Manufactured by: FLUKE

This product was added to our catalog on Thursday 25 April, 2013.